 Floor Coating

Industry: Utility Power Generation

Associated Products: Concrete Primer 1000, Floor Patch™

Problem:
This secondary containment area required repairs to cracks caused by thermal cycling and erosion. The erosion was accelerated by the occasional spilling or leaking of beach from the storage tanks.

Solution:
Complete floor and wall surfaces were first pressure washed to remove contaminates. Floor and wall areas were then etched using Devcon's B-4 Citrus Acid Etch. All cracks were repaired and sealed with Devcon's Floor Patch Fast Cure, (90 minute functional cure). Following a 1 hour partial cure of Floor Patch Fast Cure, Concrete Primer was applied to a thickness of 8 mils. Following a partial cure, (4 hours), a final coat of Epoxy Coat 7000AR (Acid Resistant) was applied to a thickness of 16 mils. Devcon's Epoxy Coat 7000AR withstands aggressive chemical operating environments.

app1 app1 app1
app1 app1  
 
   
 